alt
alt

D250-CI48-RAL7035
194629 D250-CI48-RAL7035
Y7-194629

Covers, RAL7032, HxWxD=750x375x150mmNon-transparent cover, degree of protection IP65, patented cover fasteners with integrated overpressure compensation, sealable cover fasteners, continuous foamed gasket, RAL 7032, mounting depth with mounting plate=250mm, can be used for CI bases E, X and V, lock mechanism type: actuation with tools (not accessible to unqualified personnel)

Covers, RAL7032, HxWxD=750x375x150mm
Non-transparent cover, degree of protection IP65, patented cover fasteners with integrated overpressure compensation, sealable cover fasteners, continuous foamed gasket, RAL 7032, mounting depth with mounting plate=250mm, can be used for CI bases E, X and V, lock mechanism type: actuation with tools (not accessible to unqualified personnel)

Product range 3200DRW-92
Basic function xEnergy Safety Ci
Product function Basic enclosures
Accessories Enclosure cover
Single unit/Complete unit Enclosure cover without apertures
Standards Modular system
Description EN 62208
EN 61439-2
Type cover Sealable cover fasteners
Colour Non-transparent
Width Non Transparent, RAL 7035, light gray
Height 375 mm
Mounting depth: 375 mm
For use with 250 mm
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890
>Individual enclosure for wall mounting [PV]
U-CI48…
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890
>Starting enclosure for wall mounting [PV]
40 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890
>Middle enclosure for wall mounting [PV]
38 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890
>Individual enclosure for wall mounting [PV]
35 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890
>Starting enclosure for wall mounting [PV]
80 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890
>Middle enclosure for wall mounting [PV]
75 W
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
70 W
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
850 °C; meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Not relevant to indoor installations.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
IK10
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances IP65, with base unit
10.5 Protection against electric shock Is the panel builder´s responsibility.
10.6 Incorporation of switching devices and components Protection class 2, therefore not applicable.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Ui = 1000 V AC
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
8 kV
10.10 Temperature rise Meets the product standard´s requirements.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function Is the panel builder´s responsibility.
Suitable for roof planking Meets the product standard´s requirements.
Suitable for bottom planking No
Width No
Height 375 mm
Depth 750 mm
Suitable for enclosure building width 85 mm
Suitable for enclosure building depth 375 mm
Material 250 mm
Surface finishing Plastic
Colour Other
RAL-number Grey
With de-aeration 7035
Suitable for outdoor set-up No
With cable entry Yes

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.