Basic function |
Position switches Safety position switches |
Part group reference |
AT4 |
Product range |
Adjustable roller lever |
Degree of Protection |
IP65 |
Features |
Complete unit |
Ambient temperature |
-25 - +70 °C |
Approval |
|
N/O = Normally open |
1 N/O |
N/C = Normally closed |
1 NC |
Notes |
= safety function, by positive opening to IEC/EN 60947-5-1 |
Contact sequence |
|
Contact travel■ = Contact closed□ = Contact open |
|
Positive opening (ZW) |
yes |
Enclosure covers |
Grey |
Enclosure covers |
|
Housing |
Insulated material |
Connection type |
Screw terminal |
Notes |
The operating head can be rotated at 90° intervals to adapt to the specified approach direction. For degree of protection IP65, use V-M20 (206910) cable glands with connecting thread of max. 9 mm length. |
Standards |
IEC/EN 60947 |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30 |
Ambient temperature |
-25 - +70 °C |
Mounting position |
As required |
Degree of Protection |
IP65 |
Terminal capacities >Solid |
1 x (0.75 - 2.5) 2 x (0.75 - 1.5) mm2 |
Terminal capacities >Flexible with ferrule |
1 x (0.5 - 1.5) 2 x (0.5 - 1.5) mm2 |
Repetition accuracy |
0.02 mm |
Rated impulse withstand voltage [Uimp] |
6000 V AC |
Rated insulation voltage [Ui
] |
500 V |
Overvoltage category/pollution degree |
III/3 |
Rated operational current [Ie
] >AC-15 >24 V [Ie
] |
10 A |
Rated operational current [Ie
] >AC-15 >220 V 230 V 240 V [Ie] |
6 A |
Rated operational current [Ie
] >AC-15 >380 V 400 V 415 V [Ie] |
4 A |
Rated operational current [Ie
] >DC-13 >24 V [Ie
] |
10 A |
Rated operational current [Ie
] >DC-13 >110 V [Ie
] |
1 A |
Rated operational current [Ie
] >DC-13 >220 V [Ie
] |
0.5 A |
Supply frequency |
max. 400 Hz |
Short-circuit rating to IEC/EN 60947-5-1 >max. fuse |
6 A gG/gL |
Lifespan, mechanical [Operations] |
8 x 106 |
Contact temperature of roller head |
≦ 100 °C |
Mechanical shock resistance (half-sinusoidal shock, 20 ms) >Standard-action contact |
5 g |
Mechanical shock resistance (half-sinusoidal shock, 20 ms) >Snap-action contact |
2 g |
Operating frequency [Operations/h] |
≦ 6000 |
Mechanical >Actuating force at beginning/end of stroke |
8.0/20.0 N |
Mechanical >Actuating torque of rotary drives |
0.3 Nm |
Mechanical >Max. operating speed with DIN cam |
1.4 m/s |
Mechanical >Notes |
for angle of actuation α = 30°, L = 125 mm |
Rated operational current for specified heat dissipation [In] |
6 A |
Heat dissipation per pole, current-dependent [Pvid] |
0.1 W |
Equipment heat dissipation, current-dependent [Pvid] |
0 W |
Static heat dissipation, non-current-dependent [Pvs] |
0 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-25 °C |
Operating ambient temperature max. |
+70 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Width sensor |
56 mm |
Diameter sensor |
0 mm |
Height of sensor |
83 mm |
Length of sensor |
0 mm |
Rated operation current Ie at AC-15, 24 V |
10 A |
Rated operation current Ie at AC-15, 125 V |
0 A |
Rated operation current Ie at AC-15, 230 V |
6 A |
Rated operation current Ie at DC-13, 24 V |
10 A |
Rated operation current Ie at DC-13, 125 V |
1 A |
Rated operation current Ie at DC-13, 230 V |
0.4 A |
Switching function |
Slow-action switch |
Switching function latching |
No |
Output electronic |
No |
Forced opening |
Yes |
Number of safety auxiliary contacts |
1 |
Number of contacts as normally closed contact |
1 |
Number of contacts as normally open contact |
1 |
Number of contacts as change-over contact |
0 |
Type of interface |
None |
Type of interface for safety communication |
None |
Construction type housing |
Cuboid |
Material housing |
Plastic |
Coating housing |
Other |
Type of control element |
Adjustable rotary lever |
Alignment of the control element |
Other |
Type of electric connection |
Other |
With status indication |
No |
Suitable for safety functions |
Yes |
Explosion safety category for gas |
None |
Explosion safety category for dust |
None |
Ambient temperature during operating |
25 - 70 °C |
Degree of protection (IP) |
IP65 |
Degree of protection (NEMA) |
Other |
Product Standards |
UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking |
UL File No. |
E29184 |
UL Category Control No. |
NKCR |
CSA File No. |
12528 |
CSA Class No. |
3211-03 |
North America Certification |
UL listed, CSA certified |
Specially designed for North America |
No |
Suitable for |
Branch circuits |
Max. Voltage Rating |
600 V AC |
Degree of Protection |
UL: 1, 4X; CSA: 1, 3R, 4, 4X, 12, 13 |