Accessories |
Auxiliary contact modules |
Description |
with interlocked opposing contacts Switching elements according to EN 50005 Version E combinations correspond to EN 50011 and are to be preferred. The DC operated contactor DILA(C)-22 must only be combined with 2-pole auxiliary contacts. |
Function |
for standard applications |
Number of poles |
2 pole |
Connection technique |
Screw terminals |
Conventional free air thermal current, 1 pole >Open >at 60 °C [Ith] |
|
AC-15 >220 V 230 V 240 V [Ie] |
16 A |
AC-15 >380 V 400 V 415 V [Ie] |
4 A |
N/O = Normally open |
4 A |
Mounting type |
|
Contact sequence |
2 N/O |
For use with |
Front fixing |
Type |
|
Instructions |
DILA(C)… DILM(C)7… DILM(C)9… DILM(C)12… DILM(C)15… DILM(C)17… DILM(C)25… DILM(C)32… DILM38… DILMP20… DILMP32… DILMP45… DILL… DILMF8… DILMF11… DILMF14… DILMF17… DILMF25… DILMF32… |
Distinctive number |
Front mounting auxiliary contact |
with basic device |
Interlocked opposing contacts according to IEC/EN 60947-5-1 appendix L, inside the auxiliary contact modules, also for the integrated auxiliary contacts of the DILM 7 - DILM32 Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix F (not N/C late open) |
with basic device |
|
with basic device |
60E |
Standards |
DILA(C)-40 |
Lifespan, mechanical >AC operated [Operations] |
51 |
Lifespan, mechanical >DC operated [Operations] |
DILA(C)-31 |
Component lifespan >at Ue = 230 V, AC-15, 3 A [Operations] |
42 |
Maximum operating frequency [Operations/h] |
DILA(C)-22 |
Climatic proofing |
|
Ambient temperature >Open |
IEC/EN 60947, VDE 0660, UL, CSA |
Ambient temperature >Enclosed |
10 x 106
|
Ambient temperature >Ambient temperature, storage |
10 x 106
|
Mounting position >Mounting position |
1.3 x 106
|
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Basic unit with auxiliary contact module >N/O contact |
9000 |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Basic unit with auxiliary contact module >N/C contact |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Degree of Protection |
-25 - +60 °C |
Protection against direct contact when actuated from front (EN 50274) |
- 25 - 40 °C |
Weight |
- 40 - 80 °C |
Terminal capacities >Screw terminals >Solid |
|
Terminal capacities >Screw terminals >Flexible with ferrule |
7 g |
Terminal capacities >Screw terminals >Solid or stranded |
5 g |
Terminal capacities >Screw terminals >Terminal screw |
IP20 |
Terminal capacities >Screw terminals >Pozidriv screwdriver |
Finger and back-of-hand proof |
Terminal capacities >Screw terminals >Standard screwdriver |
0.039 kg |
Terminal capacities >Screw terminals >Max. tightening torque |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
Interlocked opposing contacts within an auxiliary contact module (to IEC 60947-5-1 Annex L) |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
N/C contact (not late-break contact) suitable as a mirror contact (to IEC/EN 60947-4-1 Annex F) |
18 – 14 AWG |
Rated impulse withstand voltage [Uimp] |
M3.5 |
Overvoltage category/pollution degree |
2 Size |
Rated insulation voltage [Ui] |
0.8 x 5.5 1 x 6 mm |
Rated operational voltage [Ue] |
1.2 Nm |
Safe isolation to EN 61140 >between coil and auxiliary contacts |
|
Safe isolation to EN 61140 >between the auxiliary contacts |
Yes |
Rated operational current >Conventional free air thermal current, 1 pole >at 60 °C [Ith] |
DILM7 - DILM32 |
Rated operational current >AC-15 >220 V 230 V 240 V [Ie] |
6000 V AC |
Rated operational current >AC-15 >380 V 400 V 415 V [Ie] |
III/3 |
Rated operational current >AC-15 >500 V [Ie] |
690 V AC |
Rated operational current >DC current |
500 V AC |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >1 [24 V] |
400 V AC |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >1 [60 V] |
400 V AC |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >2 [60 V] |
16 A |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >1 [110 V] |
4 A |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >3 [110 V] |
4 A |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >1 [220 V] |
1.5 A |
Rated operational current >DC current >DC L/R ≦ 15 ms >Contacts in series: >3 [220 V] |
Switch-on and switch-off conditions based on DC-13, time constant as specified. |
Rated operational current >DC current >DC L/R ≦ 50 ms >Contacts in series: >3 [24 V] |
10 A |
Rated operational current >DC current >DC L/R ≦ 50 ms >Contacts in series: >3 [60 V] |
6 A |
Rated operational current >DC current >DC L/R ≦ 50 ms >Contacts in series: >3 [110 V] |
10 A |
Rated operational current >DC current >DC L/R ≦ 50 ms >Contacts in series: >3 [220 V] |
3 A |
Rated operational current >DC current >DC-13 (6xP) >24 V [Ie
] |
6 A |
Rated operational current >DC current >DC-13 (6xP) >60 V [Ie
] |
1 A |
Rated operational current >DC current >DC-13 (6xP) >110 V [Ie
] |
5 A |
Rated operational current >DC current >DC-13 (6xP) >220 V [Ie
] |
2.5 A |
Rated operational current >Control circuit reliability [Failure rate] |
1 A |
Short-circuit rating without welding >Short-circuit protection maximum fuse >500 V |
0.5 A |
Current heat loss at Ith >AC operated |
0.25 A |
Current heat loss at Ith >DC operated |
2.5 A |
Current heat loss at Ith >Current heat loss per auxiliary circuit at Ie (AC-15/230 V) |
1 A |
Auxiliary contacts >Pilot Duty >AC operated |
0.5 A |
Auxiliary contacts >Pilot Duty >DC operated |
0.25 A |
Auxiliary contacts >General Use >AC |
<10-8, < one failure at 100 million operations (at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA) λ |
Auxiliary contacts >General Use >AC |
10 A gG/gL |
Auxiliary contacts >General Use >DC |
2.6 W |
Auxiliary contacts >General Use >DC |
2.6 W |
Rated operational current for specified heat dissipation [In] |
0.16 CO |
Heat dissipation per pole, current-dependent [Pvid] |
|
Equipment heat dissipation, current-dependent [Pvid] |
A600 |
Static heat dissipation, non-current-dependent [Pvs] |
P300 |
Heat dissipation capacity [Pdiss] |
600 V |
Operating ambient temperature min. |
10 A |
Operating ambient temperature max. |
250 V |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
1 A |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
|
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
4 A |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
0.16 W |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
0 W |
10.2 Strength of materials and parts >10.2.5 Lifting |
0 W |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
0 W |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
-25 °C |
10.3 Degree of protection of ASSEMBLIES |
+60 °C |
10.4 Clearances and creepage distances |
|
10.5 Protection against electric shock |
Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components |
Meets the product standard´s requirements. |
10.7 Internal electrical circuits and connections |
Meets the product standard´s requirements. |
10.8 Connections for external conductors |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Does not apply, since the entire switchgear needs to be evaluated. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Does not apply, since the entire switchgear needs to be evaluated. |
10.10 Temperature rise |
Meets the product standard´s requirements. |
10.11 Short-circuit rating |
Does not apply, since the entire switchgear needs to be evaluated. |
10.12 Electromagnetic compatibility |
Meets the product standard´s requirements. |
10.13 Mechanical function |
Does not apply, since the entire switchgear needs to be evaluated. |
Number of contacts as change-over contact |
Does not apply, since the entire switchgear needs to be evaluated. |
Number of contacts as normally open contact |
Is the panel builder´s responsibility. |
Number of contacts as normally closed contact |
Is the panel builder´s responsibility. |
Number of fault-signal switches |
Is the panel builder´s responsibility. |
Rated operation current Ie at AC-15, 230 V |
Is the panel builder´s responsibility. |
Type of electric connection |
Is the panel builder´s responsibility. |
Model |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Mounting method |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Lamp holder |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Product Standards |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
UL File No. |
|
UL Category Control No. |
|
CSA File No. |
0 |
CSA Class No. |
2 |
North America Certification |
0 |
Specially designed for North America |
0 |