172273 DX-EMC12-014-FS1

Radio interference suppression filter, Single-phase, ULN= max. 250 + 10% V, 14 A, For use with: DC1
Radio interference suppression filter, Description: Single-phase, Mains voltage (50/60Hz): ULN= max. 250 + 10% V, Rated operational current: Ie= 14 A, For use with: DC1, Degree of Protection: IP00, IP20 when connected, Connection type: Connection terminal, PE stud, prefabricated cables, Weight: m 0,8 kg, Notes: Base-mounted filter, side-mounting filter, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11

Ürün Açıklaması

Radio interference suppression filter, Single-phase, ULN= max. 250 + 10% V, 14 A, For use with: DC1
Radio interference suppression filter, Description: Single-phase, Mains voltage (50/60Hz): ULN= max. 250 + 10% V, Rated operational current: Ie= 14 A, For use with: DC1, Degree of Protection: IP00, IP20 when connected, Connection type: Connection terminal, PE stud, prefabricated cables, Weight: m 0,8 kg, Notes: Base-mounted filter, side-mounting filter, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Description Single-phase
Mains voltage (50/60Hz) [ULN] max. 250 + 10% V
Rated operational current [Ie] 14 A
For use with DC1
Degree of Protection IP00
IP20 when connected
Connection type Connection terminal, PE stud, prefabricated cables
Weight [m] 0,8 kg
Notes Base-mounted filter, side-mounting filter
Standards
Environmental conditions
>Altitude
EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Degree of Protection Up to 2000 m a.s.l.; observe derating at higher altitudes m
Degree of Protection IP00
IP20 when connected
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
IP20
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Meets the product standard´s requirements.
10.8 Connections for external conductors Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Type of accessory Is the panel builder´s responsibility. The specifications for the switchgear must be observed.