106211 NH-SLS-00/160-60

Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00
H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, without safety monitoring

Ürün Açıklaması

Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00
H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, without safety monitoring
Product range 60 mm system
Basic function Busbar fuse material
Subrange Low-voltage h.b.c. switch-fuse units
Description Without fuse monitoring
With connection area cover
Mounting with snap-on mechanism
Information about equipment supplied With clamp/screw connection set
Interval between busbar centres 60 mm
Rated operational current [Ie] 160 A
400 V 160 A
690 V 160 A
Frame size 00
For use with 12 x 5/10
15 x 5/10
20 x 5/10
25 x 5/10
30 x 5/10
For use with Double T profile
Triple T profile
Connection top or bottom
Notes NH-fuse-links →#289998
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature -5 - +40
Altitude max. 2000 m m
Interval between busbar centres 60 mm
Number of poles/phases 3 n
Mounting position Vertical, horizontal
Overvoltage category/pollution degree III/3
Protection type IP30 (Operating state)
IP10 (Front cover open)
Degree of Protection IP30
Direction of incoming supply as required
Lifespan, mechanical [Operations] 1400
Weight 1.46 kg
Rated frequency [f] 50 - 60 Hz
Rated insulation voltage [Ui ] 1000 V
Rated operating mode continuous operation
Rated impulse withstand voltage [Uimp] 8 kV
Interval between busbar centres 60 mm
Overvoltage category/pollution degree III/3
Rated operational current [Ie] 160 A
690 V 160 A
Rated conditional short-circuit current AC [Iq] 50 kAeff
Utilization category AC­22B
>Rated operating voltage [Ue]
690 V AC
Utilization category AC­22B
>Rated operating current [Ie]
160 A
Utilization category AC-23B
>Rated operating voltage [Ue]
500/400 V AC
Utilization category AC-23B
>Rated operating current [Ie]
125/160 A
Utilization category AC-21B
>Rated operating voltage [Ue]
690 V AC
Utilization category AC-21B
>Rated operating current [Ie]
160 A
Electrical ≧ 200 Operations
Heat dissipation at Ith AC, without NH-SE 20 W
Number of poles 3 pole
Number of poles 3
Rated operational voltage [Ue]
>Rated operating voltage [Ue]
400 V AC
Rated frequency [f] 50 - 60 Hz
Rated operational current [Ie] 160 A
Conventional thermal current [Ith ] 160 A
Control mode Uninterrupted operation
Overvoltage category III
Rated impulse withstand voltage [Uimp] 8 kV
Power loss
>Fuse
20 W at 160 A W
Electrical ≧ 200 Operations
Lifespan, mechanical [Operations] 1400
Frame size 00
Max. rated operational current gL/gG 160 A
Max. admissible heat dissipation NH-SE [Pv] 12 W
Box terminal
>Copper band [Number of segments x width x thickness ]
6 x 9 x 0.8 mm
Flange connection
>Diameter [d]
M8 mm
Flange connection
>Stranded with cable lug
1 x 70 mm2
Flange connection
>Flat busbar [max.]
20 x 8 mm
Box terminal
>Stranded
1.5 - 70 mm2
Box terminal
>Flat conductor [Lamellenzahl x Breite x Dicke ]
6 x 9 x 0.8 mm
Mounting on busbars
>Combi-base for busbars
direct on
12 - 30 x 5/10
Double T profile
Triple T profile
Tightening torque of terminal screws 3 Nm
Lifespan, mechanical [Operations] 1400
Overvoltage category/pollution degree III/3
Operating ambient temperature min. -5 °C
Operating ambient temperature max. +40 °C
Model Fuse switch disconnector
Double interrupting No
Rated permanent current Iu 160 A
Distance between rail centre, 40 mm No
Distance between rail centre, 50 mm No
Distance between rail centre, 60 mm Yes
Distance between rail centre, 100 mm No
Distance between rail centre, 185 mm No
Max. rated operation voltage Ue AC 690 V
Conditioned rated short-circuit current Iq 50 kA
Type of electrical connection of main circuit Rail connection
Number of poles 3
Construction size fuse insert NH00
Release indication None