059777 KS150-NZM7

Cable lug, 150mm², narrow type
3 cable lugs narrow version 150mm²

Ürün Açıklaması

Cable lug, 150mm², narrow type
3 cable lugs narrow version 150mm²
Number of conductors 3/4 pole
Accessories Cable lugs
For use with NZM2(-4), PN2(-4), N2(-4)
Description Not UL/CSA approved.
Narrow tubular cable lugs for switchgear connections.
When using without cover NZM2 (-4)-XKSA, the cable lug must be insulated.
Terminal capacity 150 mm2
Instructions For detailed specifications regarding suitable types of conductors and the required crimping tool: See Heading Engineering.
Engineering notes
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance

In order to crimp cable lugs when using stranded conductors, e.g., VDE 0295 Class 2 and rounded stranded sector-shaped conductors, you will need a Klauke K22, HK60/22, or EK22 crimping tool with the following crimping dies:

  • R22/95 for 95 mm2
  • R22/120 for 120 mm2
  • R22/150 for 150 mm2
  • R22/185 for 185 mm2
  • R22/240 for 240 mm2
  • R22/300 for 300 mm2

Flexible conductors are adequate to a limited extent. They must be indent-crimped with a Klauke series 13 or series 25 crimping die.

10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Meets the product standard´s requirements.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Bolt dimension (metric) Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Connecting angle The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Number of mounting holes
Code digit
Nominal cross section 0
Surface protection 180° (horizontal)
Identification colour 1