038292 AT4/11-S/I/R416

Position switch, 1N/O+1N/C, narrow, IP65_x, roller lever
Position switch, Basic function: Position switches, Safety position switches, Part group reference: AT4, Product range: Rotary lever, Degree of Protection: IP65, Features: Complete unit, Ambient temperature: -25 - +70 °C, Design: EN 50041 Form A, Snap-action contact: Yes, Contacts N/O = Normally open: 1 N/O, Contacts N/C = Normally closed: 1 NC, Notes: = safety function, by positive opening to IEC/EN 60947-5-1, Positive opening (ZW): yes, Colour Enclosure covers: Grey, Housing: Insulated material, Connection type: Screw terminal, Standards: IEC/EN 60947

Ürün Açıklaması

Position switch, 1N/O+1N/C, narrow, IP65_x, roller lever
Position switch, Basic function: Position switches, Safety position switches, Part group reference: AT4, Product range: Rotary lever, Degree of Protection: IP65, Features: Complete unit, Ambient temperature: -25 - +70 °C, Design: EN 50041 Form A, Snap-action contact: Yes, Contacts N/O = Normally open: 1 N/O, Contacts N/C = Normally closed: 1 NC, Notes: = safety function, by positive opening to IEC/EN 60947-5-1, Positive opening (ZW): yes, Colour Enclosure covers: Grey, Housing: Insulated material, Connection type: Screw terminal, Standards: IEC/EN 60947
Basic function Position switches
Safety position switches
Part group reference AT4
Product range Rotary lever
Degree of Protection IP65
Features Complete unit
Ambient temperature -25 - +70 °C
Design EN 50041 Form A
Snap-action contact Yes
Approval 000Z083
N/O = Normally open 1 N/O
N/C = Normally closed 1 NC
Notes = safety function, by positive opening to IEC/EN 60947-5-1
Contact sequence 131S001
Contact travel■ = Contact closed□ = Contact open 131U037
Positive opening (ZW) yes
Enclosure covers Grey
Enclosure covers 116C062
Housing Insulated material
Connection type Screw terminal
Notes The operating head can be rotated at 90° intervals to adapt to the specified approach direction.
For degree of protection IP65, use V-M20 (206910) cable glands with connecting thread of max. 9 mm length.
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Ambient temperature -25 - +70 °C
Mounting position As required
Degree of Protection IP65
Terminal capacities
>Solid
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2
Terminal capacities
>Flexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mm2
Repetition accuracy 0.02 mm
Rated impulse withstand voltage [Uimp] 6000 V AC
Rated insulation voltage [Ui ] 500 V
Overvoltage category/pollution degree III/3
Rated operational current [Ie ]
>AC-15
>24 V [Ie ]
10 A
Rated operational current [Ie ]
>AC-15
>220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]
>AC-15
>380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]
>DC-13
>24 V [Ie ]
10 A
Rated operational current [Ie ]
>DC-13
>110 V [Ie ]
1 A
Rated operational current [Ie ]
>DC-13
>220 V [Ie ]
0.5 A
Supply frequency max. 400 Hz
Short-circuit rating to IEC/EN 60947-5-1
>max. fuse
6 A gG/gL
Lifespan, mechanical [Operations] 8 x 106
Contact temperature of roller head ≦ 100 °C
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Standard-action contact
5 g
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Snap-action contact
2 g
Operating frequency [Operations/h] ≦ 6000
Mechanical
>Actuating force at beginning/end of stroke
8.0/20.0 N
Mechanical
>Actuating torque of rotary drives
0.3 Nm
Rated operational current for specified heat dissipation [In] 6 A
Heat dissipation per pole, current-dependent [Pvid] 0.1 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Width sensor 40 mm
Diameter sensor 0 mm
Height of sensor 83 mm
Length of sensor 0 mm
Rated operation current Ie at AC-15, 24 V 10 A
Rated operation current Ie at AC-15, 125 V 0 A
Rated operation current Ie at AC-15, 230 V 6 A
Rated operation current Ie at DC-13, 24 V 10 A
Rated operation current Ie at DC-13, 125 V 1 A
Rated operation current Ie at DC-13, 230 V 0.4 A
Switching function Quick-break switch
Switching function latching No
Output electronic No
Forced opening Yes
Number of safety auxiliary contacts 1
Number of contacts as normally closed contact 1
Number of contacts as normally open contact 1
Number of contacts as change-over contact 0
Type of interface None
Type of interface for safety communication None
Construction type housing Cuboid
Material housing Plastic
Coating housing Other
Type of control element Rotary lever
Alignment of the control element Other
Type of electric connection Other
With status indication No
Suitable for safety functions Yes
Explosion safety category for gas None
Explosion safety category for dust None
Ambient temperature during operating 25 - 70 °C
Degree of protection (IP) IP65
Degree of protection (NEMA) Other
Product Standards UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 12528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Specially designed for North America No
Suitable for Branch circuits
Max. Voltage Rating 600 V AC
Degree of Protection UL: 1, 4X; CSA: 1, 3R, 4, 4X, 12, 13