SKU: Eaton-289809
Main switch assembly kit, handle red, on the right side
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: door coupling rotary handle with rotary drive. Extension shaft NZM…-XV4. External warning plate / marking plate in German / English. Black and yellow lightning symbol. External warning plate / marking plate can be clipped on. for enhanced busbar tag shroud on the incomer side, please order IP2X protection against contact with a finger. Red-yellow for emergency switching off. Lockable on the 0 position on the handle with max. 3 padlocks. Can be used for: NZM4(-4), N(N/O)4(-4)
Equipment supplied | Door coupling rotary handle NZM...-XV4 extension shaft External warning plate/marking plate in German/English Black and yellow lightning symbol |
Product range | Accessories |
Accessories | Main switch assembly kit for side panel mounting |
Standard/Approval | UL/CSA, IEC |
Construction size | NZM4 |
Description | Kit for use as a main switch |
Function | Actuation of the switch on the control panel side wall Switch mounting on mounting plate Red-yellow for emergency switching off |
Protection class | IP66 UL/CSA Type 4X, Type 12 |
Door interlock | Lockable on OFF with max. 3 padlocks |
Project planning information | External warning plate/designation label can be clipped on. For enhanced busbar tag shroud on the incomer side, please order IP2X protection against contact with a finger. |
Actuation | Actuation on the right |
For use with | NZM4(-4) N(S)4(-4) |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Lockable | Yes |
Colour | Red |
Suitable for emergency stop | Yes |
With extension shaft | Yes |
Suitable for power circuit breaker | Yes |
Suitable for switch disconnector | Yes |
Product Standards | UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking |
UL File No. | E140305 |
UL Category Control No. | DIHS |
CSA File No. | 022086 |
CSA Class No. | 1437-01 |
North America Certification | UL listed, CSA certified |
Degree of Protection | IEC: IP66, UL/CSA Type 4X, 12 |