284645 NZM3-XBR

Insulating surround, for NZM3
Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple. Modular functional groups make mounting flexible and simple. , rotary handle with rotary mechanism and remote operator degree of protection IP40. For oblong cut-out on doors and enclosures with material thickness´ of 1.5 - 5 mm. External warning plate / marking plate can be clipped on. NZM4-XBR can not be combined with rotary handle with rotary mechanism. Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

Ürün Açıklaması

Insulating surround, for NZM3
Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple. Modular functional groups make mounting flexible and simple. , rotary handle with rotary mechanism and remote operator degree of protection IP40. For oblong cut-out on doors and enclosures with material thickness´ of 1.5 - 5 mm. External warning plate / marking plate can be clipped on. NZM4-XBR can not be combined with rotary handle with rotary mechanism. Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)
Product range Accessories
Accessories Insulating surrounds
Standard/Approval UL/CSA, IEC
Construction size NZM3
Description For toggle levers, rotary handles with rotary drive and remote operators
Protection class IP40
For use with NZM3(-4)
PN3(-4), N(S)3(-4)
Notes

For oblong cut-out on doors and enclosures with material thicknesses of 1.5 - 5 mm.

External warning plate/designation label can be clipped on

NZM4‐XBR cannot be combined with rotary handle with rotary drive.

10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Height 132 mm
Width 193.5 mm
Depth 17.5 mm
Number of rows 0
Material Plastic
Hinging No
Quick locking No
Degree of protection (IP) IP40
Colour Black
Transparent No
Product Standards UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No. E140305
UL Category Control No. DIHS
CSA File No. 022086
CSA Class No. 1437-01
North America Certification UL listed, CSA certified