284473 NZM4-XKM2S-1600

Module plate, 2-hole, vertical, 3p, 1600A
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. insulation using NZM4(-4)-XKSA cover or NZM4(-4)-XKP phase isolator necessary. Can be used for: NZM4, N(S)4

Ürün Açıklaması

Module plate, 2-hole, vertical, 3p, 1600A
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. insulation using NZM4(-4)-XKSA cover or NZM4(-4)-XKP phase isolator necessary. Can be used for: NZM4, N(S)4
Accessories Module plate
Description Two holes
Number of conductors 3 pole
Rated current [In] ≦ 1600 A
For use with NZM4, N(S)4
Type of conductor
>Cu/Al cable
Copper cable lugs
Terminal capacities
>flexible
2 x 95 - 300 mm2
AWG/kcmil 2 x 000 - 500 mm2
Cu strip (number of segments x width x segment thickness) (2 x) 10 x 40 x 1.0
(2 x) 10 x 50 x 1.0 mm2
Copper busbar width x thickness [Width] (2 x) 40 x 10
(2 x) 50 x 10 mm
Notes

Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.

Insulation through cover NZM4(-4)-XKSA or phase isolator NZM4(4)-XKP necessary.

10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Suitable for number of poles 3
Product Standards UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No. E31593
UL Category Control No. DIHS
CSA File No. 22086
CSA Class No. 1432-01
North America Certification UL listed, CSA certified
Suitable for Refer to main component information