283472 PN2-XPA

Paralleling mechanism
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: simultaneous actuation of 2 PN switch-disconnectors of the same type mounted side-by-side. Not UL/CSA approved. 1 × rotary handle on switch (‐XD) included as standard. 1x door coupling rotary handle (-XTVD) included as standard. can be used for: PN2(-4) + PN2(-4)

Ürün Açıklaması

Paralleling mechanism
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: simultaneous actuation of 2 PN switch-disconnectors of the same type mounted side-by-side. Not UL/CSA approved. 1 × rotary handle on switch (‐XD) included as standard. 1x door coupling rotary handle (-XTVD) included as standard. can be used for: PN2(-4) + PN2(-4)
Description Simultaneous actuation of 2 PN switch-disconnectors of the same type mounted side-by-side
not UL/CSA approved
For use with PN2(-4) + PN2(-4)
Notes

PN1, PN2

  • 1 x rotary handle on switch (‐XD) supplied.
  • 1 x door coupling rotary handle (‐XTVD) supplied.
Notes

Extension shaft (-XV4(6)) additionally required for the door coupling rotary handle.

Cannot be combined with mechanical interlock, insulating surrounds, side wall operators or remote operators

For use as Emergency-Stop device

For this the door coupling rotary handle requires an exchange thumb-grip in red/yellow according to the following order nos.

  • for PN1 and PN2: NZM2‐XDGVR → 100747
  • for PN3: NZM3‐XDGVR → 100764; Note: The locking function of these thumb-grips must not be used.
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Lockable Yes
Colour Black
Suitable for emergency stop No
With extension shaft No
Suitable for power circuit breaker Yes
Suitable for switch disconnector Yes