SKU: Eaton-231230
Insulated enclosure, HxWxD=200x120x125mm, +mounting plate, NA type
Insulated enclosure, With mounting plate, Product range: CI-K small enclosures, Basic enclosures, Single unit, Degree of Protection: Front IP65, IP65, with push-through cable entry, Description: Approved for UL, CSA, smooth all round with mit sharp corners, Enclosure base RAL 9005, black, Operator only RAL 7035, light gray, Dimensions Width: 120 mm, Height: 200 mm, Depth: 125 mm, Mounting depth:: 98 mm
Product range | CI-K small enclosures |
Basic function | Basic enclosures |
Product function | Basic enclosures for North America |
Single unit/Complete unit | Single unit |
Degree of Protection | Front IP65 IP65, with push-through cable entry |
Degree of Protection | Front IP65 IP65, with push-through cable entry |
Description | Approved for UL, CSA smooth all round with mit sharp corners Enclosure base RAL 9005, black Operator only RAL 7035, light gray |
Width | 120 mm |
Height | 200 mm |
Depth | 125 mm |
Features | With mounting plate |
Mounting depth: | 98 mm |
Rated operational current for specified heat dissipation [In] | 0 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 0 W |
Static heat dissipation, non-current-dependent [Pvs] | 0 W |
Heat dissipation capacity [Pdiss] | 21.5 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +70 °C |
Degree of Protection | Front IP65 IP65, with push-through cable entry |
Surface treatment | Resistant to corrosion |
Temperature resistant | -40 °C - 120 °C (enclosure) -40 °C - +80 °C (gasket) |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire |
10.2 Strength of materials and parts >10.2.5 Lifting |
Not applicable. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Is the panel builder´s responsibility. |
10.6 Incorporation of switching devices and components | Is the panel builder´s responsibility. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Meets the product standard´s requirements. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Material housing | Plastic |
Width | 120 mm |
Height | 222 mm |
Depth | 125 mm |
With transparent cover | No |
Suitable for emergency stop | No |
Model | Surface mounting |
Degree of protection (IP) | IP65 |
Degree of protection (NEMA) | 13 |
Product Standards | UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94; IEC/EN 60947-3; CE marking |
UL File No. | E54120 |
UL Category Control No. | MITW2 |
CSA File No. | 12528 |
CSA Class No. | 3211-07 |
North America Certification | UL listed, CSA certified |
Specially designed for North America | Yes |
Degree of Protection | IEC: IP65; UL/CSA Type 1, 3R, 4X, 12, 13 – indoor and outdoor use |