SKU: Eaton-200648

200648 +IP23/05

IP23 enclosures, For use with STZ5.3 … STZ8.3
IP23 enclosure for STZ5.3 to STZ8.3, enclosure can be used with primary or secondary voltage > 110 V

Ürün Açıklaması

IP23 enclosures, For use with STZ5.3 … STZ8.3
IP23 enclosure for STZ5.3 to STZ8.3, enclosure can be used with primary or secondary voltage > 110 V
Product range Accessories
Accessories IP23 enclosures
For use with STZ5.3 … STZ8.3
Cu factor 0,00 kg
Notes

For the version with enhanced climatic proofing the transformer features a special insulating varnish. This version enables the transformer to be used in areas with a high humidity.

When ordering, the type reference must include the following details:

ETSP25(*/*)

1st wildcard ≙ Nominal input voltage

2nd wildcard ≙ Rated output voltage

Ordering example

  • Required throughput rating 55 kVA
  • Desired rated input voltage 400 V
  • Desired rated output voltage 230 V

Selection notes

SN = S x (1 - Lower voltage ⁄ Higher voltage)

= 55 kVA x (1 - 230V/400V = 23.4 kVA

SN = kVA type rating

S = Throughput rating

  • The kVA type rating is always lower than the throughput rating.
  • For version with delta stabilizing winding, please enquire.

The correct type reference is

ETSP25(400/230)

Transformer-protective circuit-breaker → 088907

Ambient temperature -25 - 40
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +40 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Material housing Steel
Width 390 mm
Height 390 mm
Depth 570 mm
With transparent cover No
Suitable for emergency stop No
Model Built-in
Degree of protection (IP) IP23
Degree of protection (NEMA) Other