2 kanallı analog giriş

2 kanallı analog giriş; 4 … 20 mA HART; Kendinden güvenli; Aşırı; mavi


This analog input module connects two field-side transformers equipped with a HART interface that are to be used in hazardous areas of Zone 0+1. The module supplies signal conditioners, reads process values via analog interface, and enables HART communication for configuring and importing dynamic variables.

The WAGO-I/O-SYSTEM 750 XTR must be installed either in Zone 2 or in a non-hazardous area.

The 24 V supply is derived from the power jumper contacts via multipliers to the field contacts (HART +).

The shield is directly connected to the DIN-rail.

The measurement input is equipped with current limitation, which limits the current to 25 mA. This module can supply the voltage for 2-wire signal conditioners.

Up to 4 HART dynamic variables (PV, SV, TV, QV) per channel can be mapped in the cyclic process image of the coupler or controller (parametrizable).

For HART communication with connected intelligent HART field devices, the HART protocol can be mapped in the cyclic process image of the coupler or controller (parametrizable).

FDT/DTM device drivers are available for select (programmable) couplers, allowing HART tool routing to the connected HART device.

The device is ideal for operation in harsh environments thanks to:

  • Extended temperature range
  • Greater immunity to impulse voltages and electromagnetic interference
  • Higher vibration and shock resistance

Note:


The analog input module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!

General information (e.g., installation regulations) on explosion protection is available in the WAGO-I/O-SYSTEM 750 XTR manuals!

Ürün Açıklaması

2 kanallı analog giriş; 4 … 20 mA HART; Kendinden güvenli; Aşırı; mavi


This analog input module connects two field-side transformers equipped with a HART interface that are to be used in hazardous areas of Zone 0+1. The module supplies signal conditioners, reads process values via analog interface, and enables HART communication for configuring and importing dynamic variables.

The WAGO-I/O-SYSTEM 750 XTR must be installed either in Zone 2 or in a non-hazardous area.

The 24 V supply is derived from the power jumper contacts via multipliers to the field contacts (HART +).

The shield is directly connected to the DIN-rail.

The measurement input is equipped with current limitation, which limits the current to 25 mA. This module can supply the voltage for 2-wire signal conditioners.

Up to 4 HART dynamic variables (PV, SV, TV, QV) per channel can be mapped in the cyclic process image of the coupler or controller (parametrizable).

For HART communication with connected intelligent HART field devices, the HART protocol can be mapped in the cyclic process image of the coupler or controller (parametrizable).

FDT/DTM device drivers are available for select (programmable) couplers, allowing HART tool routing to the connected HART device.

The device is ideal for operation in harsh environments thanks to:

  • Extended temperature range
  • Greater immunity to impulse voltages and electromagnetic interference
  • Higher vibration and shock resistance

Note:


The analog input module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!

General information (e.g., installation regulations) on explosion protection is available in the WAGO-I/O-SYSTEM 750 XTR manuals!

Number of analog inputs 2
Total number of channels (module) 2
Sinyal tipi Current
Type of signal current DC 4 … 20 mA
Sensor supply voltage DC 16,5 V; Transmitter supply UV at 20 mA
Sensor connection 2 x (2-conductor)
Giriş filtresi Parametreleştirilebilir
Giriş filtresi: parametrelerle ayarlanabilir (kanal-kanal) yes
Signal characteristic Single-ended
Arıza teşhisi Kablo kopması, ölçüm aralığı dışında
Çözünürlük [bit] 12Bit
Güç tüketimi Pmax. 1,60 W (slave´lerle (20 mA))
Bit genişliği 2 x 2 byte veri 2 x 2 byte veri + 2n x 4 byte veri (n = dinamik değişken adedi) 2 x 2 byte veri + 6 byte posta kutusu
Aşırı gerilim koruması 30 V, ters polarite korumalı
Çevirme süresi (tip.) 10ms
Messfehler, Bezugstemperatur 25°C
Messfehler, Abweichung max. vom Messbereichsendwert 0,2%
Temperaturfehler max. vom Messbereichsendwert 0,01%/K
Kendinden güvenli Ex i yes
System supply voltage DC 5 V; via data contacts
Current consumption, system supply (5 V) 25mA
Field supply voltage DC 24 V; via power jumper contacts (Ex i XTR power supply: UO = max. 27.3 V)
Current consumption, field supply (module with no external load) 26mA
Kanal başına HART aygıtları 1 aygıt (single-drop, no multi-drop)
Kanal başına HART modemleri 1 modem (multiplex değil)
Güç kaybı PV 0,62 W (slave´siz)
İzolasyon 300 VAC system/field
Dielektrik dayanımı 510 VAC/775 VDC; per EN 60870-2-1
Rated surge voltage 1 kV; Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)
Number of incoming power jumper contacts 2
Number of outgoing power jumper contacts 2
Current carrying capacity of the power jumper contacts 1A
ATEX Guideline EN/IEC 60079-0, -7, -11
Elektrik şebekesi, güvenliğe ilişkin bilgi Uo = 26,8 V; Io = 90,07 mA; Po = 603,5 mW; Kennlinie: Linear
Reaktans Ex ia IIC Lo = 1,8 mH; Co = 0,092 μF
Reaktans Ex ia IIB Lo = 16 mH; Co = 0,72 μF
Reaktans Ex ia IIA Lo = 27 mH; Co = 2.37 μF
Reaktans Ex ia I Lo = 38 mH; Co = 3,85 µF
Reaktans (The above-listed ratings do not account for the coincidental occurrence of capacitances and inductances. For ratings taking the coincidental occurrence of capacitances and inductances into account, see manual)
Connection technology: In-/Outputs 16 x CAGE CLAMP®
Connection type (1) Inputs/Outputs
Tek damarlı boylar 0,25 … 2,5 mm² / 24 … 14 AWG
İnce bükümlü kablolar 0,25 … 2,5 mm² / 24 … 14 AWG
Sıyırma uzunluğu 8 … 9 mm / 0.31 … 0.35 inch
Width 24 mm / 0.945 inch
Height 67,8 mm / 2.669 inch
DIN rayın üst kenarından yükseklik 60,6 mm / 2.386 inch
Depth 100 mm / 3.937 inch
Montaj tipi DIN 35 ray
Renk mavi
Gövde malzemesi Polycarbonate, polyamide 6.6
Ağırlık 92,9
Uygunluk işareti CE
Surrounding air (operating) temperature -40 … 70 °C
Surrounding air (storage) temperature -40 … 85 °C
Koruma sınıfı IP20
Kirlilik derecesi (5) 2 per IEC 61131-2
Çalışma yüksekliği without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); max.: 5000 m
Montaj pozisyonu horizontal (standing/lying) or vertical
Nısbi nem (yoğuşmasız) 95%
Relative humidity Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E DIN 40046-721-3 (except wind-driven precipitation, water and ice formation)
Titreşime dayanıklı acc. to IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3
Darbe direnci per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 61373
EMV-Störfestigkeit acc. to EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994
EMU: 1 - enterferans emisyonu acc. to EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3
Kirletici maddelere maruziyet Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 % 10ppm
Permissible SO2 contaminant concentration at a relative humidity 75 % 25ppm
SAP´den ambalaj tipi BOX
Country of origin DE
GTIN 4055143649506
Customs Tariff No. 85389099990