183274 EU8E-SWD-8XD-1

SWD Block module I/O module IP69K, 24 V DC, 8 outputs with separate power supply, 8 M12 I/O sockets
SWD module with IP69K degree of protection for connecting 8 digital outputs, automatic address setting, digital outputs 24 V DC 0.5 A short-circuit proof, separate M22 connector for output supply, I/O connection with one M12 socket

Ürün Açıklaması

SWD Block module I/O module IP69K, 24 V DC, 8 outputs with separate power supply, 8 M12 I/O sockets
SWD module with IP69K degree of protection for connecting 8 digital outputs, automatic address setting, digital outputs 24 V DC 0.5 A short-circuit proof, separate M22 connector for output supply, I/O connection with one M12 socket
Product range SmartWire-DT slave
Basic function Digital modules
Function For connection of digital I/O signals
Short Description with supply
Transistor 8
Connection to SmartWire-DT yes
Standards IEC/EN 61131-2
Dimensions (W x H x D) 60 x 210,3 x 34 mm
Weight 0.3 kg
Mounting Screw fixing (M4)
Mounting position As required
Power supply
>Rated operational voltage [Ue]
24 DC -15 % / +20 % V
Power supply
>Residual ripple on the input voltage
≦ 5 %
Power supply
>Protection against polarity reversal
Yes
Power supply
>Power loss [P]
1.7 W
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Air pressure (operation) 795 - 1080 hPa
Ambient temperature
>Operation [ϑ]
-25 - +55 °C
Ambient temperature
>Storage / Transport [ϑ]
-40 - +70 °C
Relative humidity
>Condensation
permissible
Relative humidity
>Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Protection type (IEC/EN 60529, EN50178, VBG 4) IP69K
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 30 g/11 ms 9 Impacts
Drop to IEC/EN 60068-2-31 [Drop height] 50 mm
Free fall, packaged (IEC/EN 60068-2-32) 0.3 m
Overvoltage category II
Pollution degree 3
Electrostatic discharge (IEC/EN 61131-2:2008)
>Air discharge (Level 3)
8 kV
Electrostatic discharge (IEC/EN 61131-2:2008)
>Contact discharge (Level 2)
4 kV
Electromagnetic fields (IEC/EN 61131-2:2008)
>80 - 1000 MHz
10 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>1.4 - 2 GHz
3 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>2 - 2.7 GHz
1 V/m
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
>Supply cable
2 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>Signal lines
1 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>SmartWire-DT cables
1 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge power cables
0.5 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge I/O cables
1 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) 10 V
Station type SmartWire-DT slave
Setting the baud rate automatic
Baud rate (data transfer speed) maximum2000 kbps
Status SmartWire-DT Green LED
SWD-IN M12 plug (A-keyed), 5 pole
SWD-OUT M12 socket (A-keyed), 5 pole
Current consumption (24V, without sensor and without I/O supply)
>Current consumption (24 V SWD supply)
79 mA
Sensor supply
>Max. current consumption per M12 I/O plug
70 mA
Sensor supply
>Overload and short-circuit proof
yes, with diagnostics
Terminal for I/O sensor
>Connection type
5-pin M12 socket (A-keyed)
Number of digital inputs/outputs 8
Quantity 8
Output current 0.5 A
Short-circuit tripping current max. 1.2 over 3 ms A
Lamp load [RLL ] ≦ 3 W
Overload proof yes, with diagnostics
Switching capacity EN 60947-5-1 utilization category DC-13
Status display outputs yellow LED
Residual ripple on the input voltage ≦ 5 %
Outputs to SmartWire-DT Yes
Output to output No
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 1.7 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +55 °C
Degree of Protection IP69K
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Supply voltage AC 50 Hz 0 - 0 V
Supply voltage AC 60 Hz 0 - 0 V
Supply voltage DC 20.4 - 28.8 V
Voltage type of supply voltage DC
Number of digital inputs 0
Number of digital outputs 8
Digital inputs configurable No
Digital outputs configurable No
Input current at signal 1 0 mA
Permitted voltage at input 20.4 - 28.8 V
Type of voltage (input voltage) DC
Type of digital output Other
Output current 0.5 A
Permitted voltage at output 20.4 - 28.8 V
Type of output voltage DC
Short-circuit protection, outputs available Yes
Number of HW-interfaces industrial Ethernet 0
Number of interfaces PROFINET 0
Number of HW-interfaces RS-232 0
Number of HW-interfaces RS-422 0
Number of HW-interfaces RS-485 0
Number of HW-interfaces serial TTY 0
Number of HW-interfaces parallel 0
Number of HW-interfaces Wireless 0
Number of HW-interfaces USB 0
Number of HW-interfaces other 0
With optical interface No
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for KNX No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems Yes
Radio standard Bluetooth No
Radio standard WLAN 802.11 No
Radio standard GPRS No
Radio standard GSM No
Radio standard UMTS No
IO link master No
System accessory Yes
Degree of protection (IP) IP69K
Type of electric connection Screw connection
Time delay at signal exchange 0.2 - 0.2 ms
Fieldbus connection over separate bus coupler possible Yes
Rail mounting possible No
Wall mounting/direct mounting Yes
Front build in possible No
Rack-assembly possible No
Suitable for safety functions No
Category according to EN 954-1 None
SIL according to IEC 61508 None
Performance level acc. EN ISO 13849-1 None
Appendant operation agent (Ex ia) No
Appendant operation agent (Ex ib) No
Explosion safety category for gas None
Explosion safety category for dust None
Width 61.6 mm
Height 212.6 mm
Depth 34 mm
North America Certification UL listed, CSA certified