177069 MINI-5

Mini compact distribution board, 1-row 5 SU, IP20
Plastic mini compact distribution board, for installing switching and protective devices, in accordance with dimension standard DIN 43 880, with an installation depth of 70 mm and a current of up to 63 A, 400 V /50 Hz, IP20 degree of protection to IEC/EN 62208, approved for building service distribution boards in accordance with IEC/EN 61439-3 VDE 0660-600-3, for surface mounting, top with 46-mm device opening, sealable as standard, white base and cover with screw closure, knockout for metric cable entries on top, bottom, and back, protection Class II, 5 space units.

Ürün Açıklaması

Mini compact distribution board, 1-row 5 SU, IP20
Plastic mini compact distribution board, for installing switching and protective devices, in accordance with dimension standard DIN 43 880, with an installation depth of 70 mm and a current of up to 63 A, 400 V /50 Hz, IP20 degree of protection to IEC/EN 62208, approved for building service distribution boards in accordance with IEC/EN 61439-3 VDE 0660-600-3, for surface mounting, top with 46-mm device opening, sealable as standard, white base and cover with screw closure, knockout for metric cable entries on top, bottom, and back, protection Class II, 5 space units.
Basic function Basic device
Product function Installation distribution boards
Product range MINI DBO
Design Surface mounted
Installation site Indoor
Type of installation Surface mounting
Door/Flap Without
Degree of Protection IP20
Colour White
Module rack Single-rail
Shroud for protection against accidental contact Plastic
Rows [Count] 1
Module units per row 5
Description IP20
Protection Class II
Plastic housing white (RAL 9003)
Cable entries Metric cable entries on top and bottom, side, back plate
PE and N terminals design Without
Equipment supplied Basic device
Standards IEC/EN 62208
RoHS (in accordance with Directive 2002/95/EC of the European Parliament and Council) conform
Ambient temperature -5 - +40 °C
Degree of Protection IP20
Protection class II (totally insulated)
Rated operational voltage [Ue] 400 V AC
Rated frequency [f] 50 Hz
Material ABS (plastic)
Colour white (RAL 9003)
Mechanical
>Impact resistance
IK05
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890
>Individual enclosure for wall mounting [PV]
11 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890
>Individual enclosure for wall mounting [PV]
13 W
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
650 °C; meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
IK05
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES IP20
10.4 Clearances and creepage distances Is the panel builder´s responsibility.
10.5 Protection against electric shock Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components Is the panel builder´s responsibility.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
2.8 kV
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Meets the product standard´s requirements.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function Meets the product standard´s requirements.
Mounting method Surface mounted (plaster)
Number of rows 1
Width in number of modular spacings 5
Type of cover None
Cover model With notch
Transparent cover/door No
Material housing Plastic
Height 140 mm
Width 120 mm
Depth 66 mm
Built-in depth 70 mm
Internal depth 60 mm
DIN-rail Yes
With mounting plate No
Extension possible No
EMC-version Yes
Colour White
RAL-number 9003
Degree of protection (IP) IP20
With lock No
Type of closure Other