174716 EU1M-SWD-NOP

SWD T-Connector Universal module IP69K
Replacement module for configured but not yet installed SWD modules with degree of protection IP69K

Ürün Açıklaması

SWD T-Connector Universal module IP69K
Replacement module for configured but not yet installed SWD modules with degree of protection IP69K
Product range SmartWire-DT slave
Basic function Universal module
Function For configured but not yet installed SWD modules connected to the SWD ribbon cable SWD4-..LR5-2S
Short Description Substitute module for configured but not yet installed SWD modules (IP67)
Connection to SmartWire-DT yes
Standards IEC/EN 61131-2
Approvals
>Approvals
UL
CSA
Dimensions (W x H x D) 85.6 x 41.1 x 20.1 mm
Weight 0.07 kg
Mounting DIN-rail, screw fixing (M4), mounting section (Clip M20)
Mounting position As required
Power supply
>Power loss [P]
0.9 W
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Air pressure (operation) 795 - 1080 hPa
Ambient temperature
>Operation [ϑ]
-25 - +70 °C
Ambient temperature
>Storage / Transport [ϑ]
-40 - +70 °C
Relative humidity
>Condensation
permissible
Relative humidity
>Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Protection type (IEC/EN 60529, EN50178, VBG 4) IP69K
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 30 g/11 ms 9 Impacts
Drop to IEC/EN 60068-2-31 [Drop height] 50 mm
Free fall, packaged (IEC/EN 60068-2-32) 0.3 m
Overvoltage category II
Pollution degree 3
Electrostatic discharge (IEC/EN 61131-2:2008)
>Air discharge (Level 3)
8 kV
Electrostatic discharge (IEC/EN 61131-2:2008)
>Contact discharge (Level 2)
4 kV
Electromagnetic fields (IEC/EN 61131-2:2008)
>80 - 1000 MHz
10 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>1.4 - 2 GHz
3 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>2 - 2.7 GHz
1 V/m
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
>Supply cable
2 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>Signal lines
1 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>SmartWire-DT cables
1 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge power cables
0.5 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge I/O cables
1 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) 10 V
Station type SmartWire-DT slave
Setting the baud rate automatic
Baud rate (data transfer speed) maximum2000 kbps
Status SmartWire-DT Green LED
SWD-IN M12 plug (A-keyed), 5 pole
SWD-OUT M12 socket (A-keyed), 5 pole
Current consumption (24V, without sensor and without I/O supply)
>Current consumption (24 V SWD supply)
45 mA
Terminal for I/O sensor
>Connection type
5-pin M12 socket (A-keyed)
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0.9 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
Degree of Protection IP69K
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Type of electrical accessory Adapter
Type of mechanical accessory Other
UL File No. E170645
North America Certification UL listed, CSA certified
Specially designed for North America No