SKU: Eaton-174715
SmartWire-DT T-Connector for IP69K I/O modules, 24 V DC, two parameterizable inputs/outputs with power supply, M12 I/O socket
SmartWire-DT module with IP67 degree of protection for connecting up to two digital input and/or output signals, parameterizable I/O type, sensor supply 24 V DC 70 mA short-circuit proof, automatic address setting, digital inputs 24 V DC, digital outputs 24 V DC 0.5 A short-circuit proof, I/O connection with one M12 socket
Product range | SmartWire-DT slave |
Basic function | Digital modules |
Function | For connection of digital I/O signals |
Short Description | Freely configurable inputs/outputs, max. 2 The outputs are short-circuit proof. |
Digital | ≤ 2 |
Transistor | ≤ 2 |
Connection to SmartWire-DT | yes |
Standards | IEC/EN 61131-2 |
Approvals >Approvals |
UL CSA |
Dimensions (W x H x D) | 85.6 x 56.9 x 20.1 mm |
Weight | 0.07 kg |
Mounting | DIN-rail, screw fixing (M4), mounting section (Clip M20) |
Mounting position | As required |
Power supply >Power loss [P] |
1.4 W |
Climatic proofing | Dry heat to IEC 60068-2-2 Damp heat as per EN 60068-2-3 |
Air pressure (operation) | 795 - 1080 hPa |
Ambient temperature >Operation [ϑ] |
-25 - +70 °C |
Ambient temperature >Storage / Transport [ϑ] |
-40 - +70 °C |
Relative humidity >Condensation |
permissible |
Relative humidity >Relative humidity, non-condensing (IEC/EN 60068-2-30) |
5 - 95 % |
Protection type (IEC/EN 60529, EN50178, VBG 4) | IP69K |
Vibrations (IEC/EN 61131-2:2008) >Constant amplitude 3,5 mm |
5 - 8.4 Hz |
Vibrations (IEC/EN 61131-2:2008) >Constant acceleration 1 g |
8.4 - 150 Hz |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 30 g/11 ms | 9 Impacts |
Drop to IEC/EN 60068-2-31 [Drop height] | 50 mm |
Free fall, packaged (IEC/EN 60068-2-32) | 0.3 m |
Overvoltage category | II |
Pollution degree | 3 |
Electrostatic discharge (IEC/EN 61131-2:2008) >Air discharge (Level 3) |
8 kV |
Electrostatic discharge (IEC/EN 61131-2:2008) >Contact discharge (Level 2) |
4 kV |
Electromagnetic fields (IEC/EN 61131-2:2008) >80 - 1000 MHz |
10 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >1.4 - 2 GHz |
3 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >2 - 2.7 GHz |
1 V/m |
Radio interference suppression (SmartWire-DT) | EN 55011 Class A |
Burst (IEC/EN 61131-2:2008, Level 3) >Supply cable |
2 kV |
Burst (IEC/EN 61131-2:2008, Level 3) >Signal lines |
1 kV |
Burst (IEC/EN 61131-2:2008, Level 3) >SmartWire-DT cables |
1 kV |
Surge (IEC/EN 61131-2:2008, Level 1) >Surge power cables |
0.5 kV |
Surge (IEC/EN 61131-2:2008, Level 1) >Surge I/O cables |
1 kV |
Radiated RFI (IEC/EN 61131-2:2008, Level 3) | 10 V |
Station type | SmartWire-DT slave |
Setting the baud rate | automatic |
Baud rate (data transfer speed) | maximum2000 kbps |
Status SmartWire-DT | Green LED |
SWD-IN | M12 plug (A-keyed), 5 pole |
SWD-OUT | M12 socket (A-keyed), 5 pole |
Current consumption (24V, without sensor and without I/O supply) >Current consumption (24 V SWD supply) |
55 mA |
Sensor supply >Max. current consumption per M12 I/O plug |
70 mA |
Sensor supply >Overload and short-circuit proof |
yes, with diagnostics |
Terminal for I/O sensor >Connection type |
5-pin M12 socket (A-keyed) |
Number of digital inputs/outputs | 2, configurable as input or output |
Quantity | 2 |
Input current | Normally 4 at 24 V DC mA |
Limit value type 1 | Low < 5V DC;High > 15V DC |
Input delay | High->Low < 0.2 ms Low->High < 0.2 ms |
Status display inputs | yellow LED |
Quantity | 2 |
Output current | 0.5 A |
Short-circuit tripping current | max. 1.2 over 3 ms A |
Lamp load [RLL ] | ≦ 3 W |
Overload proof | yes, with diagnostics |
Switching capacity | EN 60947-5-1 utilization category DC-13 |
Status display outputs | yellow LED |
Inputs for SmartWire-DT | No |
Outputs to SmartWire-DT | No |
Input to input | No |
Output to input | no |
Output to output | No |
Rated operational current for specified heat dissipation [In] | 0 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 0 W |
Static heat dissipation, non-current-dependent [Pvs] | 1.4 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +70 °C |
Degree of Protection | IP69K |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Supply voltage AC 50 Hz | 0 - 0 V |
Supply voltage AC 60 Hz | 0 - 0 V |
Supply voltage DC | 0 - 28.8 V |
Voltage type of supply voltage | DC |
Number of digital inputs | 2 |
Number of digital outputs | 2 |
Digital inputs configurable | Yes |
Digital outputs configurable | Yes |
Input current at signal 1 | 4 mA |
Permitted voltage at input | 20.4 - 28.8 V |
Type of voltage (input voltage) | DC |
Type of digital output | Other |
Output current | 0.5 A |
Permitted voltage at output | 20.4 - 28.8 V |
Type of output voltage | DC |
Short-circuit protection, outputs available | Yes |
Number of HW-interfaces industrial Ethernet | 0 |
Number of interfaces PROFINET | 0 |
Number of HW-interfaces RS-232 | 0 |
Number of HW-interfaces RS-422 | 0 |
Number of HW-interfaces RS-485 | 0 |
Number of HW-interfaces serial TTY | 0 |
Number of HW-interfaces parallel | 0 |
Number of HW-interfaces Wireless | 0 |
Number of HW-interfaces USB | 0 |
Number of HW-interfaces other | 0 |
With optical interface | No |
Supporting protocol for TCP/IP | No |
Supporting protocol for PROFIBUS | No |
Supporting protocol for CAN | No |
Supporting protocol for INTERBUS | No |
Supporting protocol for ASI | No |
Supporting protocol for KNX | No |
Supporting protocol for MODBUS | No |
Supporting protocol for Data-Highway | No |
Supporting protocol for DeviceNet | No |
Supporting protocol for SUCONET | No |
Supporting protocol for LON | No |
Supporting protocol for PROFINET IO | No |
Supporting protocol for PROFINET CBA | No |
Supporting protocol for SERCOS | No |
Supporting protocol for Foundation Fieldbus | No |
Supporting protocol for EtherNet/IP | No |
Supporting protocol for AS-Interface Safety at Work | No |
Supporting protocol for DeviceNet Safety | No |
Supporting protocol for INTERBUS-Safety | No |
Supporting protocol for PROFIsafe | No |
Supporting protocol for SafetyBUS p | No |
Supporting protocol for other bus systems | Yes |
Radio standard Bluetooth | No |
Radio standard WLAN 802.11 | No |
Radio standard GPRS | No |
Radio standard GSM | No |
Radio standard UMTS | No |
IO link master | No |
System accessory | Yes |
Degree of protection (IP) | IP69K |
Type of electric connection | Screw connection |
Time delay at signal exchange | 0 - 0.2 ms |
Fieldbus connection over separate bus coupler possible | Yes |
Rail mounting possible | Yes |
Wall mounting/direct mounting | Yes |
Front build in possible | No |
Rack-assembly possible | No |
Suitable for safety functions | No |
Category according to EN 954-1 | None |
SIL according to IEC 61508 | None |
Performance level acc. EN ISO 13849-1 | None |
Appendant operation agent (Ex ia) | No |
Appendant operation agent (Ex ib) | No |
Explosion safety category for gas | None |
Explosion safety category for dust | None |
Width | 85.6 mm |
Height | 56.9 mm |
Depth | 20.1 mm |
UL File No. | E170645 |
North America Certification | UL listed, CSA certified |
Specially designed for North America | No |