174611 DX-EMC34-100-L

Radio interference suppression filter, three-phase, low leakage current, ULN= max. 520 + 10% V, 100 A, For use with: DA1
Radio interference suppression filter, Description: three-phase, low leakage current, Mains voltage (50/60Hz): ULN= max. 520 + 10% V, Rated operational current: Ie= 100 A, For use with: DA1, Degree of Protection: IP20, Connection type: Screw terminal, PE stud, Weight: m 5,2 kg, Notes: Separate mounting, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11

Ürün Açıklaması

Radio interference suppression filter, three-phase, low leakage current, ULN= max. 520 + 10% V, 100 A, For use with: DA1
Radio interference suppression filter, Description: three-phase, low leakage current, Mains voltage (50/60Hz): ULN= max. 520 + 10% V, Rated operational current: Ie= 100 A, For use with: DA1, Degree of Protection: IP20, Connection type: Screw terminal, PE stud, Weight: m 5,2 kg, Notes: Separate mounting, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Description three-phase
low leakage current
Mains voltage (50/60Hz) [ULN] max. 520 + 10% V
Rated operational current [Ie] 100 A
For use with DA1
Degree of Protection IP20
Connection type Screw terminal, PE stud
Weight [m] 5,2 kg
Notes Separate mounting
Standards
Environmental conditions
>Altitude
EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Degree of Protection Up to 2000 m a.s.l.; observe derating at higher altitudes m
Short Circuit Current Rating
>High fault rating
IP20
Rated operational current for specified heat dissipation [In]
Heat dissipation per pole, current-dependent [Pvid] 100 kA
Equipment heat dissipation, current-dependent [Pvid]
Static heat dissipation, non-current-dependent [Pvs] 100 A
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. 60 W
Operating ambient temperature max. 0 W
Degree of Protection 0 W
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
-25 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
+50 °C
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
IP20
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Meets the product standard´s requirements.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Meets the product standard´s requirements.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function Is the panel builder´s responsibility.
Type of accessory The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Product Standards Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
UL File No. Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
North America Certification The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.