116901 BBA2-80/2TS-S

Busbar adapter, 72 mm, 80 A, DIN rail: 2
72mm busbar adapter for 60mm busbar system, 2 mounting brackets, without electrical contact, can be used universally for 1-, 2-, 3-phase applications, can be used for PKZ2, rated operational current: 80A

Ürün Açıklaması

Busbar adapter, 72 mm, 80 A, DIN rail: 2
72mm busbar adapter for 60mm busbar system, 2 mounting brackets, without electrical contact, can be used universally for 1-, 2-, 3-phase applications, can be used for PKZ2, rated operational current: 80A
Accessories Busbar adapters
For use with Approved to UL 508
For fitting to flat Cu-busbars with 60 mm between busbar centres, suitable for 5 mm and 10 mm busbar thickness
Rated operational voltage [Ue] Busbar adapters PKZ2
Rated operational current [Ie] 690 V
Adapter width 80 A
Adapter length 72 mm
DIN rail 200 mm
Adapter width 2 Quantity
For use with 72 mm
Notes PKZM4, PKE65 + DILM(C)7
PKZM4, PKE65 + DILM(C)9
PKZM4, PKE65 + DILM(C)12
PKZM4, PKE65 + DILM(C)15
PKZM4, PKE65 + DILM(C)17
PKZM4, PKE65 + DILM(C)25
PKZM4, PKE65 + DILM(C)32
PKZM4, PKE65 + DILM(C)38
PKZM4, PKE65 + DILM(C)40
PKZM4, PKE65 + DILM(C)50
PKZM4, PKE65 + DILM(C)65
Rated operational current for specified heat dissipation [In] Universal adapter for 1, 2, and 3‐phase applications, not suitable without additional UL/CSA component.
Heat dissipation per pole, current-dependent [Pvid] 80 A
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 9.3 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. 0 W
Operating ambient temperature max. -25 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
+55 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Product Standards The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
UL File No. UL 508A; CSA-C22.2 No. 14; IEC60439-1; CE marking
UL Category Control No. E300273
North America Certification NMTR; NMTR7
Specially designed for North America UL listed, certified by UL for use in Canada
Max. Voltage Rating No