116022 SWD4-8SF2-5

External device plug, SmartWire-DT, at ribbon cable for connection of SWD module
External device plug, 8-Pole can be attached at any arbitrary place on the ribbon cable. The functional elements of arbitrarily many SmartWire-DT cards can be attached to the external device plug.

Ürün Açıklaması

External device plug, SmartWire-DT, at ribbon cable for connection of SWD module
External device plug, 8-Pole can be attached at any arbitrary place on the ribbon cable. The functional elements of arbitrarily many SmartWire-DT cards can be attached to the external device plug.
Product range SmartWire-DT accessories
Basic function Plug/socket
Basic function accessories Plug-in connection
Function For connecting the ribbon cable to SmartWire-DT modules in the control panel
Description 8-pin SmartWire-DT external device plug that can be connected at any point on the ribbon cable.
External device plugs can be used to connect the function elements of any SmartWire-DT module in a control panel.
Connection to SmartWire-DT yes
For use with EU5E-SWD…
M22-SWD…
Standards IEC/EN 61131-2
EN 50178
Dimensions (W x H x D) 15 x 36.5 x 17.5 mm
Weight 0.01 kg
Mounting position As required
Power loss [P] 0 W
Note on heat dissipation not relevant
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
>constant amplitude 0.15 mm max.
8.4 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
>Constant amplitude 0.15 mm min. (RefExtrakt)
5 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
>constant acceleration 1 g max.
150 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
>constant acceleration 1 g min.
8.4 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms 9 Impacts
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Air pressure (operation) 795 - 1080 hPa
Ambient temperature
>Operation [ϑ]
-25 - +55 °C
Ambient temperature
>Storage / Transport [ϑ]
-40 - +70 °C
Ambient temperature
>Relative humidity
>Condensation
Take appropriate measures to prevent condensation
Ambient temperature
>Relative humidity
>Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Connection 1 Socket, 8-pole
Number of insertion cycles ≥ 200
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +55 °C
Degree of Protection IP20
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Type of electrical accessory Plug
Type of mechanical accessory Other
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 2324643
CSA Class No. 3211-07
North America Certification UL listed, CSA certified
Specially designed for North America No