107579 NS2-200-BT-NA

Molded Case Switch, 3p, 200A
Molded Case Switch, N2, Switch-disconnectors, 3 pole, Switching capacity SCCR 480Y/277 V 60 Hz Icu: 100 kA, S Switching capacity SCCR 600Y/347 V 60 Hz Icu: 50 kA, Rated current = rated uninterrupted current In = Iu: 200 A, Rated current = rated uninterrupted current In = Iu: 200 A, Standard/Approval: UL/CSA, IEC, Installation type: Fixed, Box terminal, Protective function: Disconnectors/main switches

Ürün Açıklaması

Molded Case Switch, 3p, 200A
Molded Case Switch, N2, Switch-disconnectors, 3 pole, Switching capacity SCCR 480Y/277 V 60 Hz Icu: 100 kA, S Switching capacity SCCR 600Y/347 V 60 Hz Icu: 50 kA, Rated current = rated uninterrupted current In = Iu: 200 A, Rated current = rated uninterrupted current In = Iu: 200 A, Standard/Approval: UL/CSA, IEC, Installation type: Fixed, Box terminal, Protective function: Disconnectors/main switches
Product range Switch-disconnectors
Protective function Disconnectors/main switches
Standard/Approval UL/CSA, IEC
Installation type Fixed
Construction size N2
Description IEC/EN 60947-2: Circuit-breakers without overcurrent (CBI-X) with main switch characteristics and isolating characteristics to IEC/EN 60204.
Number of poles 3 pole
Standard equipment Box terminal
Switch positions I, +, 0
Rated current = rated uninterrupted current [In = Iu] 200 A
Rated current = rated uninterrupted current [In = Iu] 200 A
SCCR 480Y/277 V 60 Hz [Icu] 100 kA
SCCR 480 V 60 Hz [Icu] 100 kA
SCCR 600Y/347 V 60 Hz [Icu] 50 kA
Non-delayed [Ii = In x …] 2500 A fixed
Rated surge voltage invariability [Uimp ]
>Main contacts
8000 V
Rated surge voltage invariability [Uimp ]
>Auxiliary contacts
6000 V
Rated operational voltage [Ue] 690 V AC
Rated current = rated uninterrupted current [In = Iu] 200 A
Rated current = rated uninterrupted current [In = Iu] 200 A
Rated uninterrupted current [Iu ]
>IEC/EN 61131-3 [Iu ]
250 A
Rated uninterrupted current [Iu ]
>UL 489, CSA 22.2 No. 5.1 [Iu ]
250 A
Overvoltage category/pollution degree III/3
Rated insulation voltage [Ui ] 1000 V
Other technical data (sheet catalogue) Weight
Temperature dependency, Derating
Effective power loss
Ambient temperature
>Ambient temperature, storage
- 40 - + 70 °C
Ambient temperature
>Operation
-25 - +70 °C
Mounting position
Vertical and 90° in all directions
  With residual-current release XFI:
- NZM1, N1, NZM2, N2: vertical and 90° in all directions
with plug-in adapter elements
- NZM1, N1, NZM2, N2: vertical, 90° right/left
with withdrawable unit:
- NZM3, N3: vertical, 90 ° left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions

Direction of incoming supply as required
Degree of protection
>Device
In the area of the HMI devices: IP20 (basic protection type)
Degree of protection
>Enclosures
With insulating surround: IP40
With door coupling rotary handle: IP66
Degree of protection
>Terminations
Tunnel terminal: IP10
Phase isolator and band terminal: IP00
SCCR 240 V 60 Hz [Icu] 150 kA
SCCR 480Y/277 V 60 Hz [Icu] 100 kA
SCCR 480 V 60 Hz [Icu] 100 kA
SCCR 600Y/347 V 60 Hz [Icu] 50 kA
240 V 50/60 Hz [Icm ] 330 kA
400/415 V 50/60 Hz [Icm ] 330 kA
440 V 50/60 Hz [Icm ] 286 kA
525 V 50/60 Hz [Icm ] 105 kA
690 V 50/60 H [Ic] 53 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>240 V 50/60 Hz [Icu ]
150 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>400/415 V 50 Hz [Icu ]
150 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>440 V 50/60 Hz [Icu ]
130 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>525 V 50/60 Hz [Icu ]
50 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>690 V 50/60 Hz [Icu ]
20 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>230 V 50/60 Hz [Ics ]
150 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>400/415 V 50/60 Hz [Ics ]
150 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>440 V 50/60 Hz [Ics ]
130 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>525 V 50/60 Hz [Ics ]
37.5 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>690 V 50/60 Hz [Ics]
5 kA
Lifespan, mechanical [Operations] 20000
Max. operating frequency 120 Ops/h
400 V 50/60 Hz [Operations] 10000
415 V 50/60 Hz [Operations] 10000
690 V 50/60 Hz [Operations] 7500
400 V 50/60 Hz [Operations] 6500
415 V 50/60 Hz [Operations] 6500
690 V 50/60 Hz [Operations] 5000
Standard equipment < 10 ms
Optional accessories Box terminal
Copper conductors and cables
>Box terminal
>Solid
Screw connection
Tunnel terminal
connection on rear
Copper conductors and cables
>Box terminal
>Stranded
1 x (10 - 16)
2 x (6 - 16) mm2
Copper conductors and cables
>Tunnel terminal
>Solid
1 x (25 - 185)
2 x (25 - 70) mm2
Copper conductors and cables
>Tunnel terminal
>Stranded
>1-hole
1 x 16 mm2
Copper conductors and cables
>Bolt terminal and rear-side connection
>Direct on the switch
>Solid
1 x (25 - 185) mm2
Copper conductors and cables
>Bolt terminal and rear-side connection
>Direct on the switch
>Stranded
1 x (10 - 16)
2 x (4 - 16) mm2
Al conductors, Al cable
>Tunnel terminal
>Solid
1 x (25 - 185)
2 x (25 - 70) mm2
Al conductors, Al cable
>Tunnel terminal
>Stranded
>1-hole
1 x 16 mm2
Al conductors, Al cable
>Bolt terminal and rear-side connection
>Direct on the switch
>Solid
1 x (25 - 185) mm2
Al conductors, Al cable
>Bolt terminal and rear-side connection
>Direct on the switch
>Stranded
1 x (10 - 16)
2 x (10 - 16) mm2
Cu strip (number of segments x width x segment thickness)
>Box terminal [min.]
1 x (25 - 35)
2 x (25 - 35) mm2
Cu strip (number of segments x width x segment thickness)
>Box terminal [max.]
2 x 9 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
10 x 16 x 0.8
(2x) 8 x 15.5 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
2 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Screw connection
10 x 24 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [min.]
M8
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [max.]
16 x 5 mm
Copper conductors and cables
>Box terminal
>solid
24 x 8 mm
Copper conductors and cables
>Box terminal
>Stranded
1 x (12 - 6) AWG
Copper conductors and cables
>Tunnel terminal
>solid
1 x (4 - 350) AWG/kcmil
Copper conductors and cables
>Tunnel terminal
>Stranded
>1-hole
1 x 6 AWG
Copper conductors and cables
>Bolt terminal and rear-side connection
>Direct on the switch
>solid
1 x (4 - 350) AWG/kcmil
Cu strip (number of segments x width x segment thickness)
>Box terminal [min.]
1 x (12 - 6) AWG
Cu strip (number of segments x width x segment thickness)
>Box terminal [max.]
2 x 9 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
10 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
2 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Screw connection
10 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [min.]
M8
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [max.]
16 x 5 mm
Rated operational current for specified heat dissipation [In] 20 x 5 mm
Equipment heat dissipation, current-dependent [Pvid] 200 A
Operating ambient temperature min. 38.04 W
Operating ambient temperature max. -25 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
+70 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Rated permanent current Iu The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated voltage 200 A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz 690 - 690 V
Overload release current setting 150 kA
Adjustment range short-term delayed short-circuit release 0 - 0 A
Adjustment range undelayed short-circuit release 0 - 0 A
Integrated earth fault protection 2500 - 2500 A
Type of electrical connection of main circuit No
Device construction Frame clamp
Suitable for DIN rail (top hat rail) mounting Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional No
Number of auxiliary contacts as normally closed contact Yes
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
With switched-off indicator 0
With under voltage release No
Number of poles No
Position of connection for main current circuit 3
Type of control element Front side
Complete device with protection unit Rocker lever
Motor drive integrated Yes
Motor drive optional No
Degree of protection (IP) Yes
Product Standards IP20
UL File No. UL 489; CSA-C22.2 No. 5-09; IEC 60947-2; CE marking
UL Category Control No. E148671
CSA File No. WJAZ
CSA Class No. 022086
North America Certification 4652-06
Specially designed for North America UL listed, CSA certified
Suitable for Yes
Current Limiting Circuit-Breaker Feeder circuits, branch circuits
Max. Voltage Rating No
Degree of Protection 600Y/347 V
Characteristic curve IEC: IP20; UL/CSA Type: -
Characteristic curve 1230DIA-8