107206 NZM3-XAD630

Busbar adapter, 3p, for NZM3, 630A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=630A, can be used for NZM3, PN3, N3, adapter width=140mm, rated operating voltage Ue=690VAC, screw connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved, observe derating

Ürün Açıklaması

Busbar adapter, 3p, for NZM3, 630A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=630A, can be used for NZM3, PN3, N3, adapter width=140mm, rated operating voltage Ue=690VAC, screw connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved, observe derating
Product range 60 mm system
Basic function Busbar adapters for NZM
Subrange Component adapter for circuit-breakers and switch-disconnectors
Function For surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Rated operational voltage [Ue] 690 V AC
Temperature resistant to 120°C
Rated diversity factor
Ambient temperature [°C]20304050606570
Rated operational current, max. [A] 630 605 580 554 529 517 504
Derating with respect to 630 A 1 0,96 0,92 0,88 0,84 0,82 0,80

Self-extinguishing to UL 94
Track resistance CTI 200
Number of poles 3 pole
Rated operational current [Ie] 630 A
Adapter width 140 mm
For use with NZM3,
PN3,
N(S)3
Cu factor 1,47 kg
Notes

Connection to the system possible at top or bottom via connection on rear (+)NZM3-XKR13…

Installation is with claw terminal.

Rated short-circuit switching capacity 65 kA at 480 V, 50 kA at 600 V.

Mounted by latching onto de-energized busbar.

Product Standards UL508A; CSA-C22.2 No. 14; IEC 60439-1; CE marking
UL File No. E300273
UL Category Control No. NMTR, NMTR7
CSA File No. 236217
CSA Class No. 3211-37
North America Certification UL listed, CSA certified
Conditions of Acceptability Refer to approbation report
Specially designed for North America No
Suitable for Feeder circuits
Current Limiting Circuit-Breaker Refer to approbation report
Max. Voltage Rating 600 V AC
Degree of Protection Feeder circuits