106875 LS-S02-ZB/X

Safety position switch, LS(4)…ZB, Safety position switches, 2 NC, Screw terminal
Safety position switch, Basic function: Position switches, Safety position switches, Part group reference: LS(4)…ZB, Product range: Safety position switches, Degree of Protection: IP66, Description: With the actuator inserted, the N/O contact is open and the NC contact is closed., Standards: IEC/EN 60947

Ürün Açıklaması

Safety position switch, LS(4)…ZB, Safety position switches, 2 NC, Screw terminal
Safety position switch, Basic function: Position switches, Safety position switches, Part group reference: LS(4)…ZB, Product range: Safety position switches, Degree of Protection: IP66, Description: With the actuator inserted, the N/O contact is open and the NC contact is closed., Standards: IEC/EN 60947
Basic function Position switches
Safety position switches
Part group reference LS(4)…ZB
Product range Safety position switches
Degree of Protection IP66
Description With the actuator inserted, the N/O contact is open and the NC contact is closed.
Approval 0000SPC-461
N/C = Normally closed 2 NC
Notes = safety function, by positive opening to IEC/EN 60947-5-1
Connection type Screw terminal
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Mounting position As required
Degree of Protection IP66
Terminal capacities
>Solid
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mm2
Terminal capacities
>Flexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mm2
Terminal screw PH1
Repetition accuracy 0.15 mm
Rated impulse withstand voltage [Uimp] 6000 V AC
Rated insulation voltage [Ui ] 500 V
Overvoltage category/pollution degree III/3
Rated operational current [Ie ]
>AC-15
>24 V [Ie ]
6 A
Rated operational current [Ie ]
>AC-15
>220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]
>AC-15
>380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]
>DC-13
>24 V [Ie ]
3 A
Rated operational current [Ie ]
>DC-13
>110 V [Ie ]
0.6 A
Rated operational current [Ie ]
>DC-13
>220 V [Ie ]
0.3 A
Supply frequency max. 400 Hz
Short-circuit rating to IEC/EN 60947-5-1
>max. fuse
6 A gG/gL
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Standard-action contact
25 g
Operating frequency [Operations/h] ≦ 1800
Rated operational current for specified heat dissipation [In] 6 A
Heat dissipation per pole, current-dependent [Pvid] 0.17 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Width sensor 30 mm
Diameter sensor 0 mm
Height of sensor 96 mm
Length of sensor 33.35 mm
Rated operation current Ie at AC-15, 24 V 10 A
Rated operation current Ie at AC-15, 125 V 6 A
Rated operation current Ie at AC-15, 230 V 6 A
Rated operation current Ie at DC-13, 24 V 3 A
Rated operation current Ie at DC-13, 125 V 0.8 A
Rated operation current Ie at DC-13, 230 V 0.3 A
Switching function Slow-action switch
Switching function latching No
Output electronic No
Forced opening Yes
Number of safety auxiliary contacts 2
Number of contacts as normally closed contact 2
Number of contacts as normally open contact 0
Number of contacts as change-over contact 0
Type of interface None
Type of interface for safety communication None
Construction type housing Cuboid
Material housing Plastic
Coating housing Other
Type of control element Other
Alignment of the control element Other
Type of electric connection Other
With status indication No
Suitable for safety functions Yes
Explosion safety category for gas None
Explosion safety category for dust None
Ambient temperature during operating 25 - 70 °C
Degree of protection (IP) IP65
Degree of protection (NEMA) 13