SKU: Eaton-106216
Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00
H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, with safety monitoring
Product range | 60 mm system |
Basic function | Busbar fuse material |
Subrange | Low-voltage h.b.c. switch-fuse units |
Description | With fuse monitoring With connection area cover Mounting with snap-on mechanism |
Information about equipment supplied | With clamp/screw connection set |
Interval between busbar centres | 60 mm |
Rated operational current [Ie] | 160 A |
400 V | 160 A |
Frame size | 00 |
For use with | 12 x 5/10 15 x 5/10 20 x 5/10 25 x 5/10 30 x 5/10 |
For use with | Double T profile Triple T profile |
Connection | top or bottom |
Notes | NH-fuse-links →#289998 |
Standards | IEC/EN 60255, VDE 0435 part 303 |
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Ambient temperature | -5 - +40 |
Altitude | max. 2000 m m |
Interval between busbar centres | 60 mm |
Number of poles/phases | 3 n |
Mounting position | Vertical, horizontal |
Overvoltage category/pollution degree | III/3 |
Protection type | IP30 (Operating state) IP10 (Front cover open) |
Degree of Protection | IP30 |
Direction of incoming supply | as required |
Lifespan, mechanical [Operations] | 100000000 |
Weight | 1.25 kg |
Rated operational voltage [Ue ] | 3 x 400 AC V |
Voltage range | Ue x 0.8 -1.1 V AC |
Rated frequency [f] | 50 - 60 Hz |
Own power consumption per phase (rung) | ≦ 2 (L2/L3) VA |
Rated insulation voltage [Ui ] | 400 V |
Rated operating mode | continuous operation |
Rated impulse withstand voltage [Uimp] | 4 kV |
Rated voltage [Ue] | 250 V AC |
Interval between busbar centres | 60 mm |
Overvoltage category/pollution degree | III/3 |
Rated operational current [Ie] | 160 A |
Rated conditional short-circuit current AC [Iq] | 50 kAeff |
Utilization category AC22B >Rated operating voltage [Ue] |
690 V AC |
Utilization category AC22B >Rated operating current [Ie] |
160 A |
Utilization category AC-23B >Rated operating voltage [Ue] |
500/400 V AC |
Utilization category AC-23B >Rated operating current [Ie] |
125/160 A |
Utilization category AC-21B >Rated operating voltage [Ue] |
690 V AC |
Utilization category AC-21B >Rated operating current [Ie] |
160 A |
Electrical | ≧ 150000 Operations |
Heat dissipation at Ith AC, without NH-SE | 20 W |
Number of poles | 3 pole |
Number of poles | 3 |
Rated operational voltage [Ue] >Rated operating voltage [Ue] |
400 V AC |
Rated frequency [f] | 50 - 60 Hz |
Rated operational current [Ie] | 160 A |
Conventional thermal current [Ith ] | 160 A |
Control mode | Uninterrupted operation |
Overvoltage category | III |
Utilization category | AC 15 |
Rated impulse withstand voltage [Uimp] | 4 kV |
Power loss >Fuse |
20 W at 160 A W |
Standards | EN 60947-5-1 |
Rated voltage [Ue ] | 250 V AC |
Conventional thermal current [Ith ] | 4 A |
AC-15 >Rated operational voltage [Ue ] |
230 V AC |
AC-15 >Rated operational current >AC-15 with 230 V [Ie] |
1 A |
Electrical | ≧ 150000 Operations |
Lifespan, mechanical [Operations] | 100000000 |
Max. admissible back-up fuse | 4 A gL |
Frame size | 00 |
Max. rated operational current gL/gG | 160 A |
Max. admissible heat dissipation NH-SE [Pv] | 12 W |
Box terminal >Solid |
2 x 2.5 mm2 |
Flange connection >Diameter [d] |
M8 mm |
Flange connection >Stranded with cable lug |
1 x 70 mm2 |
Flange connection >Flat busbar [max.] |
20 x 8 mm |
Box terminal >Stranded |
1.5 - 70 mm2 |
Box terminal >Flat conductor [Lamellenzahl x Breite x Dicke ] |
6 x 9 x 0.8 mm |
Pick-up/drop-out time | < 500 ms |
Mounting on busbars >Combi-base for busbars |
direct on 12 - 30 x 5/10 Double T profile Triple T profile |
Terminals | Lift terminals |
Tightening torque of terminal screws | 3 Nm |
Lifespan, mechanical [Operations] | 100000000 |
Overvoltage category/pollution degree | III/3 |
Operating ambient temperature min. | -5 °C |
Operating ambient temperature max. | +40 °C |
Model | Fuse switch disconnector |
Double interrupting | No |
Rated permanent current Iu | 160 A |
Distance between rail centre, 40 mm | No |
Distance between rail centre, 50 mm | No |
Distance between rail centre, 60 mm | Yes |
Distance between rail centre, 100 mm | No |
Distance between rail centre, 185 mm | No |
Max. rated operation voltage Ue AC | 690 V |
Conditioned rated short-circuit current Iq | 50 kA |
Type of electrical connection of main circuit | Rail connection |
Number of poles | 3 |
Construction size fuse insert | NH00 |
Release indication | Mechanical top-plate indicator |