104555 NZM2-XAD250

Busbar adapter, 3p, for NZM2, 250A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=250A, can be used for NZM2, PN2, N(S)2, adapter width=106mm, rated operating voltage Ue=690VAC, threaded connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved

Ürün Açıklaması

Busbar adapter, 3p, for NZM2, 250A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=250A, can be used for NZM2, PN2, N(S)2, adapter width=106mm, rated operating voltage Ue=690VAC, threaded connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved
Product range 60 mm system
Compact system
Basic function Busbar adapters for NZM
Subrange Component adapter for circuit-breakers and switch-disconnectors
Function For surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Rated operational voltage [Ue] 690 V AC
Temperature resistant to 120°C
Self-extinguishing to UL 94
Track resistance CTI 200
Number of poles 3 pole
Rated operational current [Ie] 250 A
Adapter width 106 mm
For use with NZM2,
PN2,
N(S)2
Cu factor 0,32 kg
Notes

Connection to the system possible at top or bottom via connection on rear (+)NZM2-XKR4…

Mounting using clamp and screw fixing.

Rated short-circuit switching capacity 65 kA at 480 V, 50 kA at 600 V.

Mounted by latching onto de-energized busbar.

Product Standards UL508A; CSA-C22.2 No. 14; IEC 60439-1; CE marking
UL File No. E300273
UL Category Control No. NMTR, NMTR7
CSA File No. 236217
CSA Class No. 3211-37
North America Certification UL listed, CSA certified
Conditions of Acceptability Refer to approbation report
Specially designed for North America No
Suitable for Feeder circuits
Current Limiting Circuit-Breaker Refer to approbation report
Max. Voltage Rating 600 V AC
Degree of Protection Feeder circuits