104554 NZM1-XAD160

Busbar adapter, 3p, for NZM1, 160A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=160A, can be used for NZM1, PN1, N(S)1, adapter width=90mm, rated operating voltage Ue=690VAC, combi base for latching onto the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved, observe derating

Ürün Açıklaması

Busbar adapter, 3p, for NZM1, 160A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=160A, can be used for NZM1, PN1, N(S)1, adapter width=90mm, rated operating voltage Ue=690VAC, combi base for latching onto the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved, observe derating
Product range 60 mm system
Compact system
Basic function Busbar adapters for NZM
Subrange Component adapter for circuit-breakers and switch-disconnectors
Function For surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Rated operational voltage [Ue] 690 V AC
Temperature resistant to 120°C
Rated diversity factor
Interior housing temperature25° C35° C45° C55° C
NZM1 ≦ 125 A RDF 1.00 1.00 0.92 0.84
NZM1  160 A RDF 1.00 0.94 0.88 0.81
         
IEC 61439: busbar ≧ 120 mm2

Self-extinguishing to UL 94
Track resistance CTI 200
Number of poles 3 pole
Rated operational current [Ie] 160 A
Adapter width 92 mm
For use with NZM1,
PN1,
N(S)1
Cu factor 0,25 kg
Notes

For switch and standard connection with box terminal.

Integrated adapters allow connection to system on top or bottom.

Increased protection against direct contact on the switch output side is possible in conjunction with IP2X protection against contact with a finger.

Latch fitting to busbar using combination stand

Can be adjusted to 5-mm and 10-mm rail thicknesses and back thanks to the integrated combination stand.

Rated short-circuit switching capacity 35 kA at 480 V.

Mounted by latching onto de-energized busbar.

Product Standards UL508A; CSA-C22.2 No. 14; IEC 61439-1; CE marking
UL File No. E140305
UL Category Control No. DIHS, DIHS7
CSA File No. 236217
CSA Class No. 3211-37
North America Certification UL listed, CSA certified
Conditions of Acceptability Refer to approbation report
Specially designed for North America No
Suitable for Feeder circuits
Current Limiting Circuit-Breaker Refer to approbation report
Max. Voltage Rating 600 V AC
Degree of Protection Feeder circuits