100663 Z-D02/R/3-36

Bus-mounted fuse base, 63A, 400 V, D02/E18, 36mm
Bus-mounted fuse base, rated operational current 63A, rated operating voltage 400V, frame size D02 E18, mounting width 36mm

Ürün Açıklaması

Bus-mounted fuse base, 63A, 400 V, D02/E18, 36mm
Bus-mounted fuse base, rated operational current 63A, rated operating voltage 400V, frame size D02 E18, mounting width 36mm
Product range 60 mm system
185 mm system
Basic function Busbar fuse material
Subrange D busbar mounted fuse devices
Basic devices
Description Including protective shroud without front and bottom plate
Delivery, empty, without screw cap, with marking plate
Type Guage ring
Rated operational current [Ie] 63 A
Rated operational voltage [Ue] 400 V AC
Frame size E18, D 02
Mounting width 36 mm
For use with 12 x 5/10
20 x 5/10
25 x 5/10
30 x 5/10
For use with Double T profile
Standards Version according to IEC/EN 60269-1, VDE 0636 Part 301
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature -25 - +55
Interval between busbar centres 60 mm
Mounting position Vertical or horizontal
Overvoltage category/pollution degree III/3
Degree of Protection IP 20 enclosed
Weight 0.15 kg
Rated frequency [f] 40 - 60 Hz
Rated impulse withstand voltage [Uimp] 6 kV
Interval between busbar centres 60 mm
Overvoltage category/pollution degree III/3
Number of poles 3 pole
Number of poles 3P
Rated operational voltage [Ue]
>Rated operating voltage [Ue]
400 V AC
Rated conditional short-circuit current tested with links [Iq] 50 kA
Rated frequency [f] 40…60 Hz
Rated operational current [Ie] 63 A
Conventional thermal current [Ith ] 63 A
Control mode Uninterrupted operation
Overvoltage category IV
Rated impulse withstand voltage [Uimp] 6 kV
Current heat loss per contact at Ie 0.5 W
Power loss
>Heat dissipation per contact with fuse link at Ie
1.5 W
Power loss
>Fuse
5.5 W
Frame size E18, D 02
Box terminal
>Solid
1.5 – 35 mm2
Terminals Lift terminals
Tightening torque of terminal screws 3 – 4 Nm
Enclosure width 201 mm
Mounting width 27 mm
Electrical hoist E18
Overvoltage category/pollution degree III/3
Operating ambient temperature min.

Fuse-links

Operating ambient temperature max. -25 °C