Ürün Açıklaması

Indicator light, without lens, + Gl 24V
Ready for use RMQ16 indicator light without lens. The pushbutton fulfils degree of protection IP65 and is approved for use world wide.
Product range RMQ16
Basic function Indicator lights
Single unit/Complete unit Single unit
Degree of Protection IP65
Connection to SmartWire-DT no
Standards IEC/EN 60947
Degree of protection, IEC/EN 60529 IP65
Ambient temperature
>Open
25 - +60 °C
Ambient temperature
>Enclosed
- 25 - 40 °C
Mounting position As required
Mechanical shock resistance > 40
according to IEC 60068-2-27
Shock duration 11 ms
Sinusoidal g
Terminal capacities 0.5 … 1.0 mm2
Blade terminal 2.8 x 0.8 mm to DIN 46244
Fast-on connectors 2.8 x 0.8 mm to DIN 46247 and IEC 60760
Rated impulse withstand voltage [Uimp] 800 V AC
Rated insulation voltage [Ui ] 250 V
Overvoltage category/pollution degree III/3
Rated operational voltage [Ue] 24 V AC
Use of insulated ferrule ISH 2,8 >24 V AC/DC recommended
>50 V AC or 120 V DC is mandatory, even on unused blade terminals
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 1 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. 25 °C
Operating ambient temperature max. +60 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Number of indicator lights 1
Colour lens Without hood
Type of lamp socket W2 x 4.6
With light source No
Rated operating voltage Ue 0 - 24 V
Voltage type AC/DC
Type of electric connection Flat plug-in connection
Construction type lens Square
Type of lens Flat
Hole diameter 16 mm
Width opening 0 mm
Height opening 0 mm
With front ring Yes
Material front ring Plastic
Colour front ring Black
Degree of protection (IP) IP65
Degree of protection (NEMA) 1