SKU: Eaton-051741
Indicator light, without lens, + Gl 24V
Ready for use RMQ16 indicator light without lens. The pushbutton fulfils degree of protection IP65 and is approved for use world wide.
Product range | RMQ16 |
Basic function | Indicator lights |
Single unit/Complete unit | Single unit |
Degree of Protection | IP65 |
Connection to SmartWire-DT | no |
Standards | IEC/EN 60947 |
Degree of protection, IEC/EN 60529 | IP65 |
Ambient temperature >Open |
25 - +60 °C |
Ambient temperature >Enclosed |
- 25 - 40 °C |
Mounting position | As required |
Mechanical shock resistance | > 40 according to IEC 60068-2-27 Shock duration 11 ms Sinusoidal g |
Terminal capacities | 0.5 … 1.0 mm2 |
Blade terminal | 2.8 x 0.8 mm to DIN 46244 |
Fast-on connectors | 2.8 x 0.8 mm to DIN 46247 and IEC 60760 |
Rated impulse withstand voltage [Uimp] | 800 V AC |
Rated insulation voltage [Ui ] | 250 V |
Overvoltage category/pollution degree | III/3 |
Rated operational voltage [Ue] | 24 V AC |
Use of insulated ferrule ISH 2,8 | >24 V AC/DC recommended >50 V AC or 120 V DC is mandatory, even on unused blade terminals |
Rated operational current for specified heat dissipation [In] | 0 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 0 W |
Static heat dissipation, non-current-dependent [Pvs] | 1 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | 25 °C |
Operating ambient temperature max. | +60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of indicator lights | 1 |
Colour lens | Without hood |
Type of lamp socket | W2 x 4.6 |
With light source | No |
Rated operating voltage Ue | 0 - 24 V |
Voltage type | AC/DC |
Type of electric connection | Flat plug-in connection |
Construction type lens | Square |
Type of lens | Flat |
Hole diameter | 16 mm |
Width opening | 0 mm |
Height opening | 0 mm |
With front ring | Yes |
Material front ring | Plastic |
Colour front ring | Black |
Degree of protection (IP) | IP65 |
Degree of protection (NEMA) | 1 |